Description
Control Panel
Series: F06
Frequency: 50/60Hz
Type: 3, 3R, 4, 4X,5, or 12 Enclosure
Watertight/ Dust-Tight
Single Throw Fusible
|
Copper Plate Line |
|||
|
FED FROM RDH2 |
|||
|
Max Fuse 60 Amp LPS-RK |
|||
|
480V |
3PH |
3W | |
|
Square D Heavy Duty Safety Switch |
|||
|
60A |
|||
|
600Vac/V~ |
600Vdc |
||
| DS COPPER PLATE LINE | |||
| Flash Hazard Boundary: 17.6in | |||
| Incident Energy at 18in: 1.15 cal/cm² | |||
| Shock Hazard when cover is removed: 480 VAC | |||
| Class Glove with Leather Protectors: 00 | |||
| Limited Approach (Fixed Circuit): 42in | |||
| Restricted Approach: 12in | |||
|
Catalog no: H362DS |
|||
|
HP Rating/Capacidad en kW (HP) |
|||
|
Volts |
ø | Std./
Est |
Max./ Max |
|
240V~ |
1 | 3 | 10 |
| 240V~ | 3 | 7.5 |
15 |
|
480V~ |
1 | 5 | 20 |
| 480V~ | 3 | 15 |
30 |
|
600V~ |
3 | 15 | 50 |
| 250V | 10 |
—– |
|
|
600V |
25 |
30 |
|
|
Lug Torque Requirements |
|
|
Line lugs, load lugs and equipment grounding lugs |
|
|
Wire Size |
Torque lb-in |
| 3 |
50 |
|
4-6 |
45 |
| 8 |
40 |
|
10-14 |
35 |
|
Conduit Entry |
|||
|
Size |
Stan. Cat
No |
Chrome Plated
Cat No |
Tight. Torque in lbs. |
|
½” |
H050 | H050CP |
800/ 90 |
|
¾” |
H075 | H075CP |
800/ 90 |
|
1” |
H100 | H100CP | 1000/
113 |
| 1 ¼” | H125 | H125CP |
1000/ 113 |
|
1 ½” |
H150 | H150CP | 1000/
113 |
| 2” | H200 | H200CP |
1600/ 181 |
|
2 ½” |
H250 | H250CP | 1600/
181 |
| 3” | H300 | H200CP |
1600/ 181 |