Description
Control Panel
Series: F06
Frequency: 50/60
Type: 3, 3R, 4, 4X, 5, or, 12 Enclosure
Water Tight/ Dust-Tight
Single Throw Fusible
|
ENIPIG LINE |
|||
|
FED FROM RDH2 |
|||
|
MAX FUSE 150 AMP LPS-RK |
|||
|
490V |
3PH |
3W | |
|
Square D Heavy Duty Safety Switch |
|||
|
200A |
|||
| 600 Vac/V~ |
600 Vdc |
||
| DS ENIPIG LINE | |||
| Flash Hazard Boundary: 21.3 in | |||
| Incident Energy at 18 in: 1.57 cal/cm² | |||
| Shock Hazard when cover is removed: 480 VAC | |||
| Class Glove with Leather Protectors: 00 | |||
| Limited Approach (Fixed Circuit): 42 in | |||
| Restricted Approach: 12 in | |||
|
Catalog no: H364DS |
|||
|
HP Rating/Capacidad en kW (HP) |
|||
|
Volts |
ø | Std./
Est |
Max./ Max |
|
240V~ |
1 | 15 | —– |
| 240V~ | 3 | 25 |
60 |
|
480V~ |
1 | 25 | 50 |
| 480V~ | 3 | 50 |
125 |
|
600V~ |
1 | 30 | 50 |
| 600V~ | 3 | 60 |
150 |
|
250V |
40 | —– | |
| 600V | 50 |
—– |
|
|
Lug Torque Requirements |
|||
| Line, Load and Neutral Lugs |
Equipment Grounding Lug |
||
|
Wire Size |
Torque lbs-in | Wire Size |
Torque lbs.-in |
|
250-6 |
275 |
14-10 |
35 |
| 8 |
40 |
||
|
6-4 |
45 | ||
| 3-2 |
50 |
||
|
Conduit Entry |
|||
|
Size |
Stan. Cat
No |
Chrome Plated
Cat No |
Tight. Torque in lbs. |
|
½” |
H050 | H050CP | 800/
90 |
| ¾” | H075 | H075CP |
800/ 90 |
|
1” |
H100 | H100CP | 1000/
113 |
| 1 ¼” | H125 | H125CP |
1000/ 113 |
|
1 ½” |
H150 | H150CP | 1000/
113 |
| 2” | H200 | H200CP |
1600/ 181 |
|
2 ½” |
H250 | H250CP | 1600/
181 |
| 3” | H300 | H200CP |
1600/ 181 |







Reviews