Description
Control Panel
Series: F06
Frequency: 50/60Hz
Type: 3, 3R, 4, 4X,5, or 12 Enclosure
Watertight/ Dust-Tight
Single Throw Fusible
Copper Plate Line |
|||
FED FROM RDH2 |
|||
Max Fuse 60 Amp LPS-RK |
|||
480V |
3PH |
3W | |
Square D Heavy Duty Safety Switch |
|||
60A |
|||
600Vac/V~ |
600Vdc |
||
DS COPPER PLATE LINE | |||
Flash Hazard Boundary: 17.6in | |||
Incident Energy at 18in: 1.15 cal/cm² | |||
Shock Hazard when cover is removed: 480 VAC | |||
Class Glove with Leather Protectors: 00 | |||
Limited Approach (Fixed Circuit): 42in | |||
Restricted Approach: 12in |
Catalog no: H362DS |
|||
HP Rating/Capacidad en kW (HP) |
|||
Volts |
ø | Std./
Est |
Max./ Max |
240V~ |
1 | 3 | 10 |
240V~ | 3 | 7.5 |
15 |
480V~ |
1 | 5 | 20 |
480V~ | 3 | 15 |
30 |
600V~ |
3 | 15 | 50 |
250V | 10 |
—– |
|
600V |
25 |
30 |
Lug Torque Requirements |
|
Line lugs, load lugs and equipment grounding lugs |
|
Wire Size |
Torque lb-in |
3 |
50 |
4-6 |
45 |
8 |
40 |
10-14 |
35 |
Conduit Entry |
|||
Size |
Stan. Cat
No |
Chrome Plated
Cat No |
Tight. Torque in lbs. |
½” |
H050 | H050CP |
800/ 90 |
¾” |
H075 | H075CP |
800/ 90 |
1” |
H100 | H100CP | 1000/
113 |
1 ¼” | H125 | H125CP |
1000/ 113 |
1 ½” |
H150 | H150CP | 1000/
113 |
2” | H200 | H200CP |
1600/ 181 |
2 ½” |
H250 | H250CP | 1600/
181 |
3” | H300 | H200CP |
1600/ 181 |
Reviews
There are no reviews yet.