Description
Control Panel
Series: F06
Frequency: 50/60Hz
Type: 3, 3R, 4, 4X, 5, or 12 Enclosure
Water Tight/Dust-Tight
Single Throw Fusible
|
WTP DIR550 CONTROL PANEL |
|||
|
FED FROM RDH2 |
|||
|
20AMP LPS-RK MAX FUSE |
|||
| 480V |
3PH |
3W | |
|
Square D Heavy Duty Safety Switch |
|||
|
30A |
|||
|
600 Vac/V~ |
600Vdc |
||
| DS WTP DIR 550 | |||
| Flash Hazard Boundary:
6.7in |
|||
| Incident Energy at 18in:
0.24 cal/cm² |
|||
| Shock Hazard when cover is removed: 480 VAC | |||
| Class Glove with Leather Protectors: 00 | |||
| Limited Approach (Fixed Circuit): 42in | |||
| Restricted Approach: 12 in | |||
|
Catalog no: H361DS |
|||
|
HP Rating/Capacidad en kW (HP) |
|||
|
Volts |
ø | Std./
Est |
Max./
Max |
| 480V~ | 1 | 3 |
7.5 |
|
480V~ |
3 | 5 | 15 |
| 600V~ | 3 | 7.5 |
20 |
|
250V |
5 | … | |
| 600V | 10 |
15 |
|
|
Lug Torque Requirements |
|
|
Line lugs, load lugs and equipment grounding lugs |
|
|
Wire Size |
Torque lb-in |
| 6 |
45 |
|
8 |
40 |
| 10-14 |
35 |
|
Crimp lugs for field installation |
|
|
Lug Wire Size |
Thomas & Betts |
| 12-10Cu |
C 10-14 |
|
8 Cu |
D 8-14 |
| 6 Cu |
E 6-14 |
|
Catalog No |
Hub Size | Tight.
Torque |
||
| Stand. | Chrome Plated | In | Lb. |
n•m |
| H050 | H050CP | ½ | 800 | 90 |
| H075 | H075CP | ¾ | 800 | 90 |
| H100 | H100CP | 1 | 1,000/
1000 |
113 |
| H125 | H125CP | 1 ¼ | 1,000/
1000 |
113 |







Reviews